| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2006 | ELECTRIC - UNDERGROUND | Approved | ||
| 06/16/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* REINSPECTION FEE DUE PRIOR TO 4TH INSPECTION. *UNCOVER FOR INSPECTION *NEED ACCESS TO GROUNDING ELECTRODE CONDUCTOR TERMINATION PLEASE DIG OUT SO I CAN OPEN. * INSTALL METAL ADDRESS TAG PER T.E.P * CARFLEX IS NOT LISTED FOR DIRECT BURIAL SO YOU CAN'T USE THIS. * CAN'T BE USED WHERE SUBJECT TO PHYSICAL DAMAGE (SUGGEST SCH.80 PVC CONDUIT USED AT PROPER DEPTH 18" BELOW FINISHED GRADE). |
|
| 05/17/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/16/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. INSTALL IRRIGATION TIMER CIRCUIT & RESCHEDULE INSPECTIONS. 2. INSTALL METAL ADDRESS LABEL (SHOULD READ 6057 S. SWEET BIRCH LN. "IRRG") 3. TERMINATE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL PER N.E.C (NOT EQUIPMENT GROUNDING LUG) |