Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00303

Parcel: 141018450

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/02/2006 ELECTRIC - UNDERGROUND Approved
06/16/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
REINSPECTION FEE DUE PRIOR TO 4TH INSPECTION.
*UNCOVER FOR INSPECTION
*NEED ACCESS TO GROUNDING ELECTRODE CONDUCTOR TERMINATION PLEASE DIG OUT SO I CAN OPEN.
* INSTALL METAL ADDRESS TAG PER T.E.P
* CARFLEX IS NOT LISTED FOR DIRECT BURIAL SO YOU CAN'T USE THIS.
* CAN'T BE USED WHERE SUBJECT TO PHYSICAL DAMAGE (SUGGEST SCH.80 PVC CONDUIT USED AT PROPER DEPTH 18" BELOW FINISHED GRADE).
05/17/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/16/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. INSTALL IRRIGATION TIMER CIRCUIT & RESCHEDULE INSPECTIONS.
2. INSTALL METAL ADDRESS LABEL
(SHOULD READ 6057 S. SWEET BIRCH LN. "IRRG")
3. TERMINATE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL PER N.E.C (NOT EQUIPMENT GROUNDING LUG)