Permit: T06EL00280


Addresses:

2008 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00280

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY FEEDER AT PANEL DIRECTORY.
2. EXPOSE UNDERGROUND CONDUCTORS OR I WILL ACCEPT GFI PROTECTION ON TRAILER FEEDER AND LIGHTING BRANCH CKT.
03/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FEEDERS TO TRAILER NEED PROTECTION NEC 527.4(B)
2. BRANCH CKT'S NEED PROTECTION NEC 527.4 (C)
3. IDENTIFY FEEDERS AND BRANCH CKT'S IN PANELS NEC 408.4
4. CORRECTIONS NEED TO BE MADE ASAP OR POWER WILL BE TERMINATED FOR SAFETY CONCERNS.