Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL00280
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY FEEDER AT PANEL DIRECTORY. 2. EXPOSE UNDERGROUND CONDUCTORS OR I WILL ACCEPT GFI PROTECTION ON TRAILER FEEDER AND LIGHTING BRANCH CKT. |
|
| 03/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FEEDERS TO TRAILER NEED PROTECTION NEC 527.4(B) 2. BRANCH CKT'S NEED PROTECTION NEC 527.4 (C) 3. IDENTIFY FEEDERS AND BRANCH CKT'S IN PANELS NEC 408.4 4. CORRECTIONS NEED TO BE MADE ASAP OR POWER WILL BE TERMINATED FOR SAFETY CONCERNS. |