Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL CKT'S AND RECEPTACLES PER PLAN. 2. IDENTIFY BRANCH CKTS (NEW IN PANEL) 3. GROUNDS IN SUB-PANEL NEED AN EQUIPMENT GROUND CONDUCTOR BACK TO SERVICE - NOT TO WATER PIPE. 4. GROUND BAR CAN'T HAVE SELF TAP SCREWS TO ENCLOSURE. 5. KITCHEN RECEPTS FOR COUNTER NEED GFI PROTECTION AND MAKE SURE THEY WORK PROPERLY/WIRED PROPERLY. 6. HAVE W.M COVER WITH OPEN HOLE. 7. ROMEX WITHIN 6' OF ATTIC ACCESS NEEDS PROTECTION NEC 334.23 |