Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00279

Parcel: 125042860


Addresses:

1927 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL CKT'S AND RECEPTACLES PER PLAN.
2. IDENTIFY BRANCH CKTS (NEW IN PANEL)
3. GROUNDS IN SUB-PANEL NEED AN EQUIPMENT GROUND CONDUCTOR BACK TO SERVICE - NOT TO WATER PIPE.
4. GROUND BAR CAN'T HAVE SELF TAP SCREWS TO ENCLOSURE.
5. KITCHEN RECEPTS FOR COUNTER NEED GFI PROTECTION AND MAKE SURE THEY WORK PROPERLY/WIRED PROPERLY.
6. HAVE W.M COVER WITH OPEN HOLE.
7. ROMEX WITHIN 6' OF ATTIC ACCESS NEEDS PROTECTION NEC 334.23