Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED CHECK #1049 $108.00 AFTER HOURS INSPECTION |
|
| 06/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR WORKING ON JOB. |
|
| 05/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MEET WITH CONTRACTOR TO DISCUSS JOB |
|
| 04/24/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO COVER CONDUIT 1. OLD PANEL NOT ALLOWED AS A JUNCTION BOX USE AN APPROVED BOX. 2. WE HAVE BOX OVERFILL AND EXPOSED CONDUCTORS IN LAUNDRY ROOM. 3. WHAT ARE WE DOING WITH NM CABLE EXPOSED IN LAUNDRY ROOM? 4. FINISH PREVIOUS ITEMS 3, 5, & 6 |
|
| 03/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT RISER WITH 1/4" MINIMUM HARDWARE NOT DRYWALL SCREWS. 2. MAINTAIN CLEARANCES FROM GAS VENT 3' 3. LABEL BREAKERS. 4. PLEASE UNCOVER CONDUIT TO UNIT #2 FOR INSPECTION. 5. VERIFY DERATING OF CONDUCTORS PER 310.15 6. TIGHTEN LOOSE FITTINGS 7. PLEASE VERIFY CONNECTIONS AT UNIT #2 TO CHECK IF NEW OR EXISTING CIRCUITS. |