Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ISOLATE BRANCH WIRING THAT GOES TO NEW SERVICE #2 FOR EXISTING SERVICE #1 BRANCH CIRCUITS WHICH FEED UNIT #2 NOW GO IN AND OUT OF SERVICE PANEL #1 ISOLATE THEM AND KEEP THEM APART. 2. GROUND J-BOX BETWEEN BOTH SERVICES. 3. 250 NEC 2002 REQUIRES THAT GROUND SYSTEMS BE BONDED TOGETHER. 4. INSTALL A ROOF JACK ON NEW SERVICE #2 CORRECT AND RECALL. 5. STRAP 1" CONDUIT BELOW NEW SERVICE. |