Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* NOTE PRIOR TO FINAL CHANGE THE RECEPTACLE OUT TO GFCI WEATHERPROOF EQUIP. |
|
| 02/09/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE TO SERVICE (GROUND ROD) 2. RISER SUPPORTS TO BE 1/4" MINIMUM HARDWARE 3. ENTRANCES ABOVE CURRENT PARTS TO USE AN APPROVED SEALING DEVICE. 4. FILL UNUSED OPENINGS IN BACK OF PANEL 5. A GUY BACK SUPPORT WILL BE NEEDED FOR RISER |