Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/28/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADD SERVICE UPGRADE TO THIS PERMIT 2) SUPPORT BOX FOR GFI OUTLET UNDER PANEL AND INSTALL BUBBLE TYPE COVER 3) USE PROPER FITTING TO TERMINATE LB INTO PANEL ON SIDE. PVC ADAPTOR NOT APPROVED 4) USE 1/4" MINIMUM BOLTS TO SUPPORT RISER CONDUIT 5) J-BOX OUTSIDE MUST BE RATED FOR OUTSIDE USE |