Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T06EL00209
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2006 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 02/10/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEED GROUNDING ELECTRODE FOR SERVICE 2. NEED CONTINUOUS GROUND WIRE TO GROUND ROD 3. SELF TA SCREWS NOT ALLOWED 4. INSTALL HOLD DOWN FOR MAIN OR GO INTO MAIN LUGS. 5. NEED BOND BUSHING FOR MAST 6. BOND NEUTRALS AND GROUNDS TO PANEL |