Permit: T06EL00199

Parcel: 125090570


Addresses:

2725 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/05/2007 ELECTRIC - FINAL Approved
02/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*PROVIDE ACCESS TO INTERIOR FOR INSPECTION SAW NOTE, WAITED 15 MINUTES?
02/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*GROUND J-BOX ABOVE SERVICE
CHECK TO MAKE SURE PANEL DIRECTORY IS MARKED CORRECTLY
ALL KITCHEN COUTNER OUTLETS NEED GFI PROTECTION AND NEED TO BE WIRED PROPERLY
DISPOSAL CORD TO BE BETWEEN 18" & 36"
INSTALL ANTI TIP DEVICE FOR RANGE
NEED GFI PROTECTION FOR BATH OUTLETS
NEED ENCLOSED TRIM OVER SHOWER
NEED SMOKE DETECTOR IN EACH BEDROOM
INSTALL HEATER OR PUT CONDUCTORS IN J-BOS
HALL J-BOX NEEDS TO BE PROPERLY GROUNDED NO SELF TAP SCRED
FIX SERVICE DEAD FRONT COVER SO IT DOES NOT CONTACT CONDUCTORS