Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHEN CONDUCTORS #4 OR LARGER GO THRU A RACEWAY, CONDUIT OR ENTER A BOX OR CABINET, NEED TO USE AN INSULATED BUSHING TO PROTECT CONDUCTORS FROM EDGES NEC 300-4F 2) 3/4" EMT CONDUIT COMING INTO EAST SIDE OF CABINET NEEDS TO BE SUPPORTED 3) 2" ? AND NIPPLES LOOSE 4) STRAP #4 BARE COPPER WIRE BELOW SERVICE TO WALL 5) WATER BOND TO GAS IN CLOSET OK 6) HAVE CONTRACTOR CORRECT AND RECALL |