Permit: T06EL00188

Parcel: 133101560


Addresses:

8561 E LEE PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SPLICE TO BE LISTED FOR COPPER TO ALUMINUM CONNECTION
2) ANTI-OXIDE COMPOUND LISTED FOR COPPER TO ALUMINUM CONDUCTORS-GROUNDS
3) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINALS
4) FOAM IN BACK OF PANEL IS COMBUSTIBLE AND FLAMABLE
02/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SEPARATE GROUNDING EQUIPMENT CONDUCTOR
2. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS.
3. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINAL LUGS.
4. MARKING TAPE TO ENCIRLCE CONDUCTOR
5. FILL UNUSED OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE PRODUCT.