Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SPLICE TO BE LISTED FOR COPPER TO ALUMINUM CONNECTION 2) ANTI-OXIDE COMPOUND LISTED FOR COPPER TO ALUMINUM CONDUCTORS-GROUNDS 3) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINALS 4) FOAM IN BACK OF PANEL IS COMBUSTIBLE AND FLAMABLE |
|
| 02/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEPARATE GROUNDING EQUIPMENT CONDUCTOR 2. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS. 3. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINAL LUGS. 4. MARKING TAPE TO ENCIRLCE CONDUCTOR 5. FILL UNUSED OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE PRODUCT. |