Permit: T06EL00187

Parcel: 13304006H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE RECALL AFTER ENERGIZED
10/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WHERE DO UNDERGROUND CONDUITS GO TO? ARE WE EXTENDING EXISTING RUNS? WHERE DOES OLD MEET NEW?
2. WHAT IS 60 AMP BREAKER FOR - WHAT IS 20 AMP 1 POLE BREAKER FOR?
3. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
4. ID HIGH LEG ON BRANCH CIRCUIT CONDUCTORS.
5. WHAT LOAD IS TO BE CONNECTED TO NEW SERVICE?
09/25/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. UNCOVER CONDUITS IN GROUND FOR INSPECTION.
2. SHEET METAL SCREWS NOT ALLOWED FOR
GROUNDING 250.8
3. CLEAN SURFACES UNDER LUGS -- 250.12
4. LABEL SERVICE METERS
5. TIGHTEN LOOSE FITTINGS
6. SUPPORT PVC CONDUITS ABOVE GROUND.
7. FILL UNUSED OPENING.