Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LABLE SUB-PANEL CLEARLY 2. LAND ALL GROUNDS IN SUB-PANEL 3. BARE CONDUCTOR FRM INTERIOR HOUSE PANEL IS A NEUTRAL - INSULATE IT AND LAND ON NEUTRAL BAR. 4. LAND EQUIPMENT GROUND FROM FEEDER TO EQUIPMENT GROUND BAR. 5. COVER GROUND RODS AND CONDUCTOR (GEC) 6. REPAIR FRONT SUB-PANEL COVER SO IT WORKS PROPERLY. |