Permit: T06EL00180

Parcel: 110111160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*RECAL AFTER CROSSOVER
FILL UNUSED OPENINGS IN BACK OF PANEL 110.12 ALSO USE A NEW COMBUSTABLE PRODUCT AROUND SE CABLE
MAINTAIN WORKING CLEARANCES 110.26