Permit: T06EL00166

Parcel: 122153240


Addresses:

3131 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/02/2006 ELECTRIC - FINAL Approved IVRS - Inspection :$
PANEL IS STILL NOT CORRECTLY MARKED
02/01/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BURY GROUNDING ELECTRODE CONDUCTOR OR SECURE TO STRUCTURE SURFACES.
2. TIGHTEN GAS BOND SET SCREW.
3. BOND TO HOUSE WATER PIPE INSTEAD OF SPRINKLER PIPE AND TIGHTEN CLAMP SCREWS.
4. PANEL DIRECTORY IS NOT LABELED PROPERLY (GFI)
5. USE INSULATED CONDUCTOR FOR NEUTRAL ON SUB-PANEL AND IDENTIFY IT (WHITE)