Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL00130
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO CLEAR RECALL AFTER CROSS OVER |
|
01/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210$ 1. RUN BOND WIRE TIGHT TO BUILDING SURFACE AND SECURE 2. BOND ALL METAL PIPING SYSTEMS TO SERVICE NEC 250.104 3. BOND METER ENCLOSURE 4. BOND SERVICE NIPPLE |