Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/24/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ISOLATE NEUTRAL & EQUIP. GROUNDING AT SUB PANEL (BUS & CONDUCTORS) AND BOND EQ. GROUNDING BUS & ISOLATE NEUTRALS & NEUTRAL BUS BAR. 2. USE PROPER BRAND BREAKERS FOR G.E. PANEL 3. EXPOSE PANEL FEEDER CONDUIT 4. EXPOSE GROUNDING ELECTRODE CONDUCTOR & GROUND RODS. 5. E.M.T. NOT TO BE USED U.G. 6. PROVIDE PLANS & PERMIT 7. EXPOSE ALL CONDUIT FOR INSPECTION. 8. BOND METALLIC PIPING & WALL CASING. |