Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/30/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RISER CONDUIT NOT PER TEP SPEC'S PLEASE CALL TEP INSP. TO INSPECT RECALL C.O.T INSPECTORS. 2. GROUND WIRE AT WATER BOND NEEDS TO PASS THRU HOLE ON CLAMP. 3. 2" CONDUIT INTO SERVICE ENCLOSURE SHOULD BE RIGID CONDUIT THREADED INTO HUB AT TOP, NO EMT SET SCREW. |
|
| 08/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED ROMEX CONNECTOR ON GROUND WIRE COMING INTO BOTTOM OF SERVICE. 2. USE ONE MORE 15 AMP BREAKER CANNOT DOUBLE LUG TWO WIRES ON ONE BREAKER DAN THEY USED A SET SCREW CONN ON RISER |
|
| 08/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. #14 WIRE ON 20 AMP BREAKERS CHANGE BREAKERS TO 15 AMP. 2. NO COMPLIANCE WITH NOTE #1 - CLAMP #4 WIRE AT BOTTOM OF PANEL 3. VERIFY WATER PIPE BOND. |
|
| 04/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. INSTALL CLAMP WHERE #4 BARE GROUND WIRE ENTERS SERVICE PANEL. 2. MC CABLE NOT TERMINATED PROPERLY INTO PANEL. LISTED MC CONNECTORS REQUIRED FOR TERMINATION. 3. NO LOCKNUT ON 1 1/4" FITTING INTO PANEL. 4. WATER & GAS PIPING MUST BE BONDED TO SERVICE. 5. BUBBLE COVER REQUIRED ON GFI RECEPT. BELOW PANEL. 6. INSIDE HOUSE REWIRED WITH MC CABLE NOT PER CODE NO BOXES UNDER CEILING FIXTURES. 7. OBTAIN PERMIT FOR INSIDE WORK & THIS SERVICE OF A QUALIFIED ELECTRICIAN TO DO THE WORK. |