Permit: T06EL00113

Parcel: 119044270


Addresses:

3561 S 8TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/30/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RISER CONDUIT NOT PER TEP SPEC'S PLEASE CALL TEP INSP. TO INSPECT RECALL C.O.T INSPECTORS.
2. GROUND WIRE AT WATER BOND NEEDS TO PASS THRU HOLE ON CLAMP.
3. 2" CONDUIT INTO SERVICE ENCLOSURE SHOULD BE RIGID CONDUIT THREADED INTO HUB AT TOP, NO EMT SET SCREW.
08/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ROMEX CONNECTOR ON GROUND WIRE COMING INTO BOTTOM OF SERVICE.
2. USE ONE MORE 15 AMP BREAKER CANNOT DOUBLE LUG TWO WIRES ON ONE BREAKER

DAN THEY USED A SET SCREW CONN ON RISER
08/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. #14 WIRE ON 20 AMP BREAKERS
CHANGE BREAKERS TO 15 AMP.
2. NO COMPLIANCE WITH NOTE #1 - CLAMP #4 WIRE AT BOTTOM OF PANEL
3. VERIFY WATER PIPE BOND.
04/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. INSTALL CLAMP WHERE #4 BARE GROUND WIRE ENTERS SERVICE PANEL.
2. MC CABLE NOT TERMINATED PROPERLY INTO PANEL. LISTED MC CONNECTORS REQUIRED FOR TERMINATION.
3. NO LOCKNUT ON 1 1/4" FITTING INTO PANEL.
4. WATER & GAS PIPING MUST BE BONDED TO SERVICE.
5. BUBBLE COVER REQUIRED ON GFI RECEPT. BELOW PANEL.
6. INSIDE HOUSE REWIRED WITH MC CABLE NOT PER CODE NO BOXES UNDER CEILING FIXTURES.
7. OBTAIN PERMIT FOR INSIDE WORK & THIS SERVICE OF A QUALIFIED ELECTRICIAN TO DO THE WORK.