Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/18/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PERMANENTLY ADDRESS SERVICE CLOSE OFF OPEN CIRCUIT BREAKER SLOTS USE SQ D CIRCUIT BREAKER AS DIRECTED ON CABLE GAS METER CANNOT BE BELOW ELECT SERVICE MUST COMPLY WITH 2002 NEC 110-26 CLEARANCE REQUIRMENTS MAKE SURE TO USE GROUND BUSHINGS ON 2" EMT CONNECTORS GOING INTO BOTTOM OF GUTTER DUE TO UNPROTECTED CONDUCTORS VERIFY CONDUCTORS GOING UP THUR RISER ARE SUNLIGHT RESISTANT. PHYSICALLY PROTECT SE CABLE EXPOSED BEETWEEN SERVICE |