Permit: T06EL00073

Parcel: 132110250


Addresses:

2705 S KRAMER AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/01/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/18/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* PERMANENTLY ADDRESS SERVICE
CLOSE OFF OPEN CIRCUIT BREAKER SLOTS
USE SQ D CIRCUIT BREAKER AS DIRECTED ON CABLE
GAS METER CANNOT BE BELOW ELECT SERVICE MUST COMPLY WITH 2002 NEC 110-26 CLEARANCE REQUIRMENTS
MAKE SURE TO USE GROUND BUSHINGS ON 2" EMT CONNECTORS GOING INTO BOTTOM OF GUTTER DUE TO UNPROTECTED CONDUCTORS
VERIFY CONDUCTORS GOING UP THUR RISER ARE SUNLIGHT RESISTANT.
PHYSICALLY PROTECT SE CABLE EXPOSED BEETWEEN SERVICE