Permit: T06EL00071


Addresses:

201 W PRESIDENT ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/06/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*OK TO CLEAR INCR
CALL FRO FINAL AFTER TIE IN
02/01/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT RISER CONDUIT WITHIN 3' OF TOP OF PANEL
2) 2 GROUND RODS REQUIRED 6' MINIMUM APART
3) BOND WATER AND GAS PIPING
4) CHANGE PERMIT DESCRIPTION TO 100 AMP SERVICE UPGRADE NOT 60
5) STRAP #4 BARE COPPER WIRE TO WALL. ALSO CHECK WITH TEP-METER TO HIGH