Inspection History Details
Permit: T06EL00071
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*OK TO CLEAR INCR CALL FRO FINAL AFTER TIE IN |
|
| 02/01/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT RISER CONDUIT WITHIN 3' OF TOP OF PANEL 2) 2 GROUND RODS REQUIRED 6' MINIMUM APART 3) BOND WATER AND GAS PIPING 4) CHANGE PERMIT DESCRIPTION TO 100 AMP SERVICE UPGRADE NOT 60 5) STRAP #4 BARE COPPER WIRE TO WALL. ALSO CHECK WITH TEP-METER TO HIGH |