Permit: T06EL00068

Parcel: 113072450


Addresses:

1380 E ADELAIDE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ITEM FROM 1/23/06 INSP. NOT CORRECTED
02/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NO ANSWER AT 400-6570
DOG IN YARD AT HOUSE
01/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 99 BURY GAS AND WATER BOND CONDUCTOR OR SECURE TO STRUCTURE
TIGHTEN SET SCREWS FOR BOND CLAMPS AND SCRAPE PAINT UNDER CLAMP
DERATE CONDUCTORS IN CONDUIT PER NEC 310.15
GROUND J BOX AND USE W.P CONNECTOR ON TOP ( NOT SET SCREW)
CLEAN OUT BOTTOM OF J BOX
MAX 15 AMP BREAKER FOR 14 GA WIRE
SEAL HOLE FOR L.G TO ATTIC
MAKE SURE PANEL DIRECTORY IS CORRECTLY MARKED
01/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*NO ANSWER @ DOOR-YARD GATE LOCKED AND DOG IN YARD