Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM FROM 1/23/06 INSP. NOT CORRECTED |
|
| 02/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NO ANSWER AT 400-6570 DOG IN YARD AT HOUSE |
|
| 01/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 99 BURY GAS AND WATER BOND CONDUCTOR OR SECURE TO STRUCTURE TIGHTEN SET SCREWS FOR BOND CLAMPS AND SCRAPE PAINT UNDER CLAMP DERATE CONDUCTORS IN CONDUIT PER NEC 310.15 GROUND J BOX AND USE W.P CONNECTOR ON TOP ( NOT SET SCREW) CLEAN OUT BOTTOM OF J BOX MAX 15 AMP BREAKER FOR 14 GA WIRE SEAL HOLE FOR L.G TO ATTIC MAKE SURE PANEL DIRECTORY IS CORRECTLY MARKED |
|
| 01/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*NO ANSWER @ DOOR-YARD GATE LOCKED AND DOG IN YARD |