Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/11/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLAMP HOLDING WATER BOND - SCREW LOOSE ON WIRE 2. J-BOX SOUTH OF SERVICE - ISOLATE NEUTRAL TIED TO GROUND, RUN WHITE TAPED NEUTRAL FROM SERVICE TO BARE STRANDED NEUTRAL FROM HOUSE 3. BLUE WIRE NUTS TO FULLY ENCLOSE HOT CONDUCTORS BARE WIRE SHOWING PASSED END OF WIRE NUT |