Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL00038

Parcel: 128111120


Addresses:

222 S NEMA PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/12/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/11/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CLAMP HOLDING WATER BOND - SCREW LOOSE ON WIRE
2. J-BOX SOUTH OF SERVICE - ISOLATE NEUTRAL TIED TO GROUND, RUN WHITE TAPED NEUTRAL FROM SERVICE TO BARE STRANDED NEUTRAL FROM HOUSE
3. BLUE WIRE NUTS TO FULLY ENCLOSE HOT CONDUCTORS
BARE WIRE SHOWING PASSED END OF WIRE NUT