Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/10/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. GROUND ELECTRODE CONDUCTOR TO TERMINATE AT NEUTRAL BAR - USE IRREVERSIBLE SPLICE TO EXTEND. 2. RISER NOT INSTALLED FLUSH TO BOTTOM OF ENCLOSURE DUE TO ANGLE INTO GROUND BELOW PANEL. THIS WAS EXISTING, CONTR. REPLACED SERVICE PANEL DUE TO VANDALISM, USE BOND BUSHING ON RISER & BOND TO ENCLOSURE |