Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 01/24/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* BURY OR SUPPORT GROUNDING ELECTRODE CONDUCTOR & WATER BOND (#6 TO SMALL FOR WATER BOND) *RISER IS TOO SMALL PER T.E.P A 2" RISER IS THE MIN. ALLOWABLE *INSTALL METAL ADDRESS TAG PER I.R.C & TEP REQUIREMENTS *INSTALL #4 GAS BOND *INSTALL CONDUIT ON UNISTRUT OR EQUIVALENT ON ROOF *INSTALL PROPER COLOR CONDUCTORS (CODE DOESN'T ALLOW TAPING A CONDUCTOR SMALLER THAN #4) *ROMEX STAPLES NOT ADEQUATE FOR SECURING ELECTRODE CONDUCTOR *DRIVE GROUND RODS FLUSH OR BELOW FINISHED GRADE *USE 1/4" HARDWARE OR BETTER FOR RISER SUPPORT & MOUNTING OF EQUIPMENT *INSTALL LOCKNUT BETWEEN LB & PANEL TO ASSURE PANEL - CONDUIT BONDING *I'LL NEED INTERIOR ACCESS TO COMPLETE INSPECTION * SUGGEST HIRING A LIC. ELECTRICAL CONTRACTOR FOR ASSISTANCE |