Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210$ 1. GROUNDING ELECTRODE CONDUCTOR IS A TRIPPING HAZARD AND COULD BE DAMAGED - PLEASE SECURE IT CLOSELY TO SURFACES IN WALKWAY AND ON ROOF, ALSO NEED TO DRIVE RODS FLUSH AND PROTECT OR BURY CONDUCTOR BETWEEN RODS. 2. NEED TO INSTALL LOCK NUT ON L.B. ENTERING PANEL (IT'S LOOSE) |
|
| 01/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*FIX ROOF BOND WIRE SO IS NOT TRIP HAZARD. OK FOR RECONNECT, BUT FINISH SERVICE FOR FINAL. OK TEP RECN. CALLED IN 12:40 PM |