Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/31/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* MEET WITH PAUL OF AEROSTAR ELECTRIC. HE WILL TAKE CARE OF PROBLEMS AND RECALL FOR POWER CLEARANCE AS DISCUSSED. |
|
| 05/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE. 2. PLEASE VERIFY 2ND GROUND ROD. 3. RECEPTACLE COVER TO BE AS PER 406.8 4. NEW CONDUITS COVERED IN NEW STUCCO - CANNOT INSPECT FITTING OR SUPPORTS. 5. ENTRANCES ABOVE CURRENT CARRYING PARTS TO USE APPROVED SEALING DEVICE. 6. SECURE CABLES & CONDUCTOR TO PANEL WITH APPROVED CONDUCTORS. 7. OLD DISCONT NOT ALLOWED FOR JUNCTION BOX. 8. USE APPROVED FITTING OR NIPPLE TO CONNECT JUNCTION BOX. 9. NEED TO SEE CONNECTION OF INTERIOR CABLES. 10. PLEASE VERIFY PRMIT FOR NEW WIRING OF CIRCUITS AND A/C |