Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/10/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 06/30/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU CANNOT UPGRADE THE BREAKER PANEL AT THIS SERVICE TO 100 AMP UNLESS YOU UPGRADE THE ENTIRE SYSTEM INCLUDING THE METER BASE & RISER CONDUCTORS. THERE ARE TWO SERVICES FED FROM 60 AMP. DROP & METER BASES. |
|
| 04/24/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 2 GROUND RODS REQUIRED 6' MIN. APART, BOND WATER PIPING. 2. SERVICE ON RIGHT OF 426 NOT PER CODE - WILL REFER #428 TO DNR, CITY OF TUCSON. 3. GROUND LUG IN #426 PANEL NEEDS TO HAVE NUT & BOLT TO FASTEN - NO SHEET METAL SCREW. 4. INSTALL CLAMP WHERE #4 GROUND ENTERS PANEL. 5. NO DOUBLE LUGGING. 6. INSTALL LISTED HUB ABOVE PANEL. 7. NEW WIRING IN 426 IS REPLACING EXISTING OLD WIRING NO PERMIT REQUIRED. |
|
| 01/09/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*I.D BOTH METERS SERVICE SERVICES NOT GROUNDED PROPERLY SECOND METER TO RIGHT HAS BEEN MODIFIED, BREAKER NOT INSTALLED PER CODE. MUST BE ADDRESSED AND INSTALLED PER CODED, WILL BE SUBJECT TO POWER KILL. SMOKE DETECTORS REQUIRED IN SLEEPING AREAS, NEW WIRING IN KITCHEN, BATHROOM, REQUIRE PERMIT & PLANS. COOLER CORD CANOT BE SPLICED WITH OPEN SPLICES. WORK TO BE DONE BY C-11 LICENSED CONTR. HAVE CONTRACTOR CONTACT RAY MAJUTA OR DAN SANTA CRUZ PRIOR TO NEXT INSPECTION. 791-5550 EXT 1136 IF NO INSPECTIONS IS CALLED IN, INSPECTOR WILL FOLLOW UP 30 DAYS. |