Permit: T06EL00002

Parcel: 130055180


Addresses:

2314 S TUCSON SV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/10/2006 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) OK TO CLEAR FOR CONSTRUCTION POWER
2) ALL ELECTRICAL WIRING TO HOUSE DISCONNECTED AT PANEL AND 1 CIRCUIT TO A GFI PROTECTED RECEPTACLE INSTALLED FOR CONST. ANY NEW WIRING REQUIRES A PERMIT
01/04/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND WIRES AND NEUTRALS TO BE ISOLATED IN SUB-PANEL
2) SOME 2-WIRE CIRCUITS IN SUB-PANEL MUST ONLY FEED 2 WIRE RECEPTACLES
3) WATER HEATER ROOM-INSTALL LIGHT, PHYSCIALLY PROTECT ROMEX, STORAGE ROOM-PROTECT ROMEX UP TO 8'
4) SMOKE DETECTORS REQUIRED IN SLEEPING AREAS
5) ALL DEVICE PLATES TO BE INSTALLED
6) CLOSET LIGHT TO BE RE-SECURED
7) KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED
8) BATHROOM RECEPTACLE TO BE GFI PROTECTED
9) RE-SECURE GROUND TO WATER LINE AND RE-CLAMP
10) BOND GAS LINE
11) REMOVE WIRING IN PLAY HOUSE AND ORANGE CORD AT BACK PORCH
12) WEATHER PROOF ROOF OUTLETS
13) REMOVE OUTSIDE WIRING EAST SIDE AND ? RECEPTACLE
14) CORRECT NORTH PORCH LIGHT WIRING