Inspection Status: Violation
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 07/26/2006 |
INSP - INITIAL CODE ENFORCMENT |
|
Violation |
OWNER GRANTED PERMISSION FOR INSPECTION. IMPROPER ELECTRICAL CONNECTION FOR RV AT THE REAR YARD. 30 AMP RV CORD CONNECTED TO ORANGE OUTSIDE TEMPORARY CORD AND CONNECTED TO 20 AMP CIRCUIT IN THE GARAGE. SEWAGE FOR RV NOT CONNECTED TO AN APPROVED SEWAGE SYSTEM. AREA SHOWED PUDDLING AND MESQUITOS. OCCUPANT OF RV WAS PRESENT. CORD WAS DISCONNECTED. MAIN STRUCTURE ELECTRICAL SERVICE DOOR DOES NOT CLOSE PROPERLY AND MAIN LINE DOUBLE LUGGED TO A SUBPANEL LOCATED AT THE NORTHWEST CORNER OF THE PROPERTY. CONDUIT AT BOTTOM OF MAIN SERVICE IS LOOSE AND LACKS PROPER GROMMET. SUBPANEL LACKS DEAD FRONT AND MAIN SHUT OFF. 3 CONDUIT EXITS AT THE BOTTOM OF THE SUBPANEL ARE LOOSE AND UNSECURED. WIRING FROM SUBPANEL LEADS TO GARAGE SOUTH OF THE MAIN DWELLING. SUBPANEL IN THE GARAGE. LIGHTS LACK JUNCTION BOXES TO CORRECTLY CONNECT LIGHTS. EXPOSED ROMEX WIRING THROUGHOUT THE GARAGE. INTERIOR: LACK OF SMOKE DETECTORS IN THE BEDROOMS. POSSIBLE ADDITIONS ON THE WEST SIDE OF THE DWELLING. INCLUDED ONE LIVING ROOM, ONE BEDROOM AND ONE FULL BATHROOM. RM |