Permit: T06CM06566

Parcel: 11301146Z


Addresses:

1763 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM06566

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/12/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
03/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING NOT PER PLAN.
2. NEED GFI FOR KITCHEN RECEPTACLES - NEC 210.8 B
3. STRAP EMT - NEC 358.30 AND TIGHTEN ALL FITTINGS 358.42
4. J-BOX IN CEILING HAS OPEN HOLES, IMPROPER USE OF WIRE NUTS.
5. GROUND ALL METAL BOXES - NEC 250
6. SECURE RACEWAYS IN CEILINGS - NEC 300.11
7. INSTALL ALL J-BOX COVERS

CLEAN UP CEILING ELECTRICAL