Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06566
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/12/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
03/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT PER PLAN. 2. NEED GFI FOR KITCHEN RECEPTACLES - NEC 210.8 B 3. STRAP EMT - NEC 358.30 AND TIGHTEN ALL FITTINGS 358.42 4. J-BOX IN CEILING HAS OPEN HOLES, IMPROPER USE OF WIRE NUTS. 5. GROUND ALL METAL BOXES - NEC 250 6. SECURE RACEWAYS IN CEILINGS - NEC 300.11 7. INSTALL ALL J-BOX COVERS CLEAN UP CEILING ELECTRICAL |