Permit: T06CM06560

Parcel: 11005014C


Addresses:

2920 N SWAN RD #106


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06560

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE REVISED PANEL DIRECTORY LABELED
AS PER 408.4 -- NO ABBREVIATIONS
2. EFFECTIVELY GROUND SWITCHES AT EXTENDER RINGS
3. WRAP GROUND CONDUCTOR 3/4 OF A TURN UNDER TERMINAL SCREW
4. MAINTAIN WORKING SPACE & CLEARANCE W/H DISCONNECT
5. ATTACH FIXTURE BOX (CHANDELIER) TO GRID
6. FILL UNUSED OPENINGS IN BOX
7. PLEASE OPEN ALL EQUIPMENT TO INSPECT LABELING
8. PLEASE PROVIDE ROOF ACCESS