Permit: T06CM06556

Parcel: 141315850

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM06556

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 FRAMING Approved IVRS - Inspection :*
03/15/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KIT CEILING PEX 12" TO LIGHT CANS
2) TWO 1/2 PEX AT REFRIDGERATOR ?
3) BLOCK MECH KIT. CEILING
4) DRYER DUCT OPEN JOINT CEILING
5) OVEN DUCT OUT OF WALL
6) NO H20 IN POTABLE OR DWV
7) MORE VERT NAILS AT GARAGE SHEAR
8) SHIM OVER NOTCHED STUDS GARAGE
9) ROLL FLAT VENT TO UPPER 1/3 OF PIPE SHOWER
10) SHIM ALL OVER NOTCHED STUDS
11) SECURE H20 SERV.
12) ROMEX CONNECTION AT LAUNDRY
13) BLOCK 2ND FLOOR TUB SIDES
14) WIRE ALL FANS SMART BOX
15) OVER NOTCHED STUD 2ND FLOOR TUB DIVERTER
16) 2ND FLOOR NAIL ALL SHEARWALLS, BOTTOM PLATES FOR PLAN AND BOLT ALL 1ST FLOOR PLATES
02/26/2007 FRAMING Partial Approval IVRS - Inspection :*
1) WIND BRACE MISSING WEST SIDE
02/22/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT READY FOR INTERMEDIATES