Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM06545
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/19/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GAS NOT PER PLAN, ALSO, 2" SUPPLY HAS A REDUCER IN THE RUN. 2. SEDIMENT TRAPS AT WH & FURNACES 3. SECURE WH VENT CONNECTOR W/3 SCREWS AT EACH JOINT 4. EXPANSION TANK REQUIRED 5. CAP UNUSED WATER PIPING 6. PROVIDE A SOLID CONNECTION AT BACKFLOW PREVENTION ASSEMBLIES. 7. PROVIDE BACKFLOW CERTS AFTER CORRECTING 8. PROVIDE SLOPE, SUPPORT AND INSTALL PROPERLY, USING PVC PRIMER ON INDIRECT DRAIN PIPING AT SODA FOUNTAIN. 9. SEPARATE CONDENSATE AND ICE MAKER DRAIN PIPING. 10. USE PROPER DRAINAGE FITTINGS ON SANITIZE COMP ID WASTE. 11. AC CONDENSATE DRAINS NOT PROPERLY TERMINATED. |
|
| 04/17/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GAS PIPING NOT INSTALLED PER PLAN ALSO, SEDIMENT TRAPS REQUIRED. 2. GAS PIPING NOT PROPERLY SUPPORTED 3. DRAIN PIPING NOT PER KEY NOTES. 4. PERM CAP PIPING REQUIRING DEMO 5. HAVE CONDENSATE PIPING INSPECTED BY MECHANICAL INSPECTOR 6. ALL SAFETY DEVICES SHALL BE INSTALLED FOR FINAL. |