Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM06545

Parcel: 11206219B


Addresses:

2574 N CAMPBELL AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06545

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/19/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. GAS NOT PER PLAN, ALSO, 2" SUPPLY HAS A REDUCER IN THE RUN.
2. SEDIMENT TRAPS AT WH & FURNACES
3. SECURE WH VENT CONNECTOR W/3 SCREWS AT EACH JOINT
4. EXPANSION TANK REQUIRED
5. CAP UNUSED WATER PIPING
6. PROVIDE A SOLID CONNECTION AT BACKFLOW PREVENTION ASSEMBLIES.
7. PROVIDE BACKFLOW CERTS AFTER CORRECTING
8. PROVIDE SLOPE, SUPPORT AND INSTALL PROPERLY, USING PVC PRIMER ON INDIRECT DRAIN PIPING AT SODA FOUNTAIN.
9. SEPARATE CONDENSATE AND ICE MAKER DRAIN PIPING.
10. USE PROPER DRAINAGE FITTINGS ON SANITIZE COMP ID WASTE.
11. AC CONDENSATE DRAINS NOT PROPERLY TERMINATED.
04/17/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. GAS PIPING NOT INSTALLED PER PLAN
ALSO, SEDIMENT TRAPS REQUIRED.
2. GAS PIPING NOT PROPERLY SUPPORTED
3. DRAIN PIPING NOT PER KEY NOTES.
4. PERM CAP PIPING REQUIRING DEMO
5. HAVE CONDENSATE PIPING INSPECTED BY MECHANICAL INSPECTOR
6. ALL SAFETY DEVICES SHALL BE INSTALLED FOR FINAL.