Permit: T06CM06545

Parcel: 11206219B


Addresses:

2574 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06545

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
NOTE: ALL 120V 15 & 20 AMP
RECEPTACLES IN KITCHEN TO HAVE GFI PROTECTION --
NEC 210.8
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION ONLY
1. REPAIR/CLOSE OPEN WIRING AND J-BOX AT FRONT EXTERIOR BY STREET.
2. CHECK EMERGENCY LIGHTING - MAKE SURE ALL IS WORKING
(MAIN DINING)
3. NEED MORE PERMANENT, CORRECTLY IDENTIFIED PANEL DIRECTORIES
4. PROVIDE GFI PROTECTION FOR ALL 120V KITCHEN RECEPTACLES
5. WIRING NOT PER PLAN, PROVIDE LETTER FROM ARCHITECT FOR ANY CHANGES.