Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Cancelled
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06545
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Cancelled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 04/24/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR ELECTRICAL COVER IN WALLS |
|
| 02/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXTEND EXTERIOR (WALL) EAST J-BOXES TO FINISHED WALL, INCLUDES EXISTING J-BOXES 2. ANGLED FITTINGS TO PAN BOXES NOT ALLOWED IN WALL NEC 300.1 3. PROVIDE NAIL PLATES AS NEEDED - NEC 330.30 4. PROVIDE BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED - NEC 314 5. HALL 3 GANG BOX NOT PROPERLY MOUNTED - NEC 314.23 |