Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PRIMARY & SECONDARY DRAINS CANNOT BE TERMINATED TOGETHER. USE AN OVERFLOW SENSOR IF NECESSARY MARK DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. CONDENSOR NOT PROPERLY FUSED. AIR BALANCE OK |
|
| 05/28/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE SECONDARY DRAIN AT AIR HANDLER 2. ALL PVC PIPE TO BE PRIMED 3. REFRIGERATION PIPING NOT PROPERLY INSULATED 4. RETURN AIR DUCT NOT PROPERLY SEALED 5. PROVIDE FILTER FOR OUTSIDE AIR 6. PROVIDE BALANCING DAMPER FOR OUTSIDE AIR 7. PROVIDE ISOLATORS UNDER CONDENSOR PER PLANS 8. SEAL KNOCKOUT IN SERVICE DISCONNECT BOX 9. SUPPLY AIR NOT SEALED AT UNIT |