Permit: T06CM06535

Parcel: 12308002B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/06/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
02/01/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEE GENERAL PLUMBING NOTE #4
NOTES: PLUMBERS TAPE NOT APPROVED
2. SEE GENERAL PLUMBING NOTE #14 -- 3/4" AND LARGER TO HAVE 1" THICK INSULATION.
3. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP
4. REMEMBER: ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.