Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06535
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AT AC 1. HAVE WRONG SIZE FUSES 2. PROPERLY IDENTIFY PHASE CONDUCTORS 3. HAVE UNDERSIZED EQUIPMENT GROUND FROM DISCONNECT TO UNIT 4. STRAP FLEX WITHIN 12" OF TERMINATIONS - USE PROPER ANCHORS 1. NEED GFI PROTECTION FOR ALL EXTERIOR RECEPTACLES 2. NEED GFI PROTECTION FOR BATHROOM RECEPTACLES 3. DISHWASHER MISSING CORD 4. FAN COIL GROUND UNDERSIZED/STRAP FLEX |