Permit: T06CM06535

Parcel: 12308002B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06535

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
AT AC
1. HAVE WRONG SIZE FUSES
2. PROPERLY IDENTIFY PHASE CONDUCTORS
3. HAVE UNDERSIZED EQUIPMENT GROUND FROM DISCONNECT TO UNIT
4. STRAP FLEX WITHIN 12" OF TERMINATIONS - USE PROPER ANCHORS

1. NEED GFI PROTECTION FOR ALL EXTERIOR RECEPTACLES
2. NEED GFI PROTECTION FOR BATHROOM RECEPTACLES
3. DISHWASHER MISSING CORD
4. FAN COIL GROUND UNDERSIZED/STRAP FLEX