Permit: T06CM06535

Parcel: 12308002B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM06535

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL WARNING RIBBON MIN. 12" ABOVE SECONDARY RACEWAYS, OK COVER AFTER THAT
2. ADD SERVICE UPGRADE AND CABLE DROP TO PERMIT
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALL AND CEILING COVER
02/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NAIL PLATES ARE NEEDED IN SEVERAL LOCATIONS FOR MEC AND L.V WIRING - NEC 300
2. CHECK BOX FILL - NEC 314.16
3. UNDERGROUND SCREWS - DO NOT OVERLAP,
NO INSULATION UNDER SCREWS - NEC 110.13
4. IDENTIFY WHITE USED AS HOT - NEC 200.6
5. FINISH DEMO AS MUCH AS ACCESSIBLE