Permit: T06CM06533

Parcel: 13348128F

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06533

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/18/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE INSULATION 8' IN & 8' OUT OF WATER HEATER WATER SUPPLIES PER 2003 ENERGY CONSERVATION CODE.
2. PROVIDE WATER BACKFLOW PROTECTION FOR SUBMERGED INLET TO MOLD GRINDER IN LAB WITH CERTIFICATION.
3. FINISH INSTALL OF ALL FIXTURES OR HAVE PLAN REVISED DELETING THEM
4. TURN ON TRAP PRIMER TO FLOOR SINK AFTER REPAIR OF LEAK. REPAIR LEAKS AT ANGLE STOPS.
04/11/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
HAD PRE-CON MEETING WITH STEVE (CACTUS MEDICAL)
MARCO (MARCO PLUMBING, DAVID (STARSKY'S) ABOUT NOTE #19 ON PLANS CONCERNING AIR SYSTEM REQUIREMENT TO MEET NFPA 99 STANDARDS
STARSKYS SHALL HAVE MEDICAL GAS TEST & MEDICAL GAS FINAL ADDED TO PERMIT CARD, HAVE INSPECTION BY CITY AND INDEPENDENT VERIFIER.