Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1.ALL INTERNAL BACKFLOW CERTS RECEIVED 2. PROVIDE MIN SLOPE AND SUPPORT ON ALL INDIRECT PIPING 3. USE PIPE SUPPORTS NOT P-TAPE 4. PROVIDE CLEARANCE ABOVE FLOOR UNDER SINK FOR CLEANING 5. SUPPORT PIPING OFF OF SINK STAND |
|
| 02/09/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL FIXTURES SHALL BE INSTALLED W/WATER ON 2. CORRECT ANY DRIPPING FAUCETS INSTALL AERATORS 3. INDIRECT WASTE LINES SHALL BE SUPPORTED AS CLOSE AS POSSIBLE TO EQUIPMENT AND DRAIN W/SUPPORTS NOT MORE THAN 4' APART. 4. 1/4" PER FOOT SLOPE REQUIRED 5. 1" AIR GAP MIN. 1 1/2" INDIRECT WASTES SHALL HAVE WYE PATTERN FITTINGS AT HORIZONTAL CHANGES OF DIRECTION 6. HAND SINK REQUIRES A CLEANOUT. CORRECT DRIPS. TEST BACKFLOW AT ICE MACHINE. COFFEEMAKER REQUIRES BACKFLOW. 7. WILL COLLECT BACKFLOW CERTS. ON NEXT INSP. |
|
| 02/06/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/19/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. YOU NEED TO GET ROUGH AND INTERMEDIATE PLUMBING APPROVED BEFORE CALLING FOR FINAL. 2. PIPING NOT PER PLAN; SIZE, ALSO 3 COMP SINK 3. HAND SINKS CANNOT DRAIN INDIRECT 4. HAND SINKS CANNOT ATTACH TO CLEANOUT OF EXISTING SINK. 5. INDIRECT DRAINS CANNOT CONNECT DIRECTLY TO DRAIN PIPING. 6. INDIRECT DRAINS CANNOT COMBINE, AND MUST BE PROPERLY SUPPORTED AND SHALL BE PIPED W/DRAINAGE FITTINGS AND PROPERLY SLOPED. 7. TRANSITION GLUE NOT APPROVED FOR USE INSIDE BUILDING 8. FERNCO COUPLINGS NOT APPROVED FOR USE INSIDE BUILDING 9. NO EXPOSED PEX - SUBJECT TO DAMAGE 10. NO SPLITTING OF WATER LINES DOWNSTREAM OF RPS 11. LIST MAY NOT BE COMPLETE. |