Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 01/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PREVIOUS ITEM EXCEPT #2 -- WAITING ON LOCATIONS OF LISTING LABELS ON EQUIPMENT. |
|
| 01/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WORK HAS BEEN DONE TO INTERIOR SINCE THE LAST PERMITTED ELECTRICAL INSPECTIONS. PLEASE HAVE THIS ADDED TO PERMIT AND HAVE ELECTRICIAN CHECK. 2. PLEASE VERIFY LISTING OF LIGHTING CONTROLLER AND LIGHTING 110.3 3. BOXES EXTENDED IN DRYWALL MORE THAT 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 4. PLEASE VERIFY INSPECTIONS FOR PVC CONDUIT IN SLAB. 5. PLANS CALL FOR 8 NEW GFI'S WE ONLY HAVE 6 6. FILL UNUSED OPENING AND CLOSE BOX COVERS. 7. PLEASE HAVE QUALIFIED ELECTRICIAN MEET ME ON SITE. |