Permit: T06CM06511

Parcel: 133160500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
01/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PREVIOUS ITEM EXCEPT #2 -- WAITING ON LOCATIONS OF LISTING LABELS ON EQUIPMENT.
01/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WORK HAS BEEN DONE TO INTERIOR SINCE THE LAST PERMITTED ELECTRICAL INSPECTIONS. PLEASE HAVE THIS ADDED TO PERMIT AND HAVE ELECTRICIAN CHECK.
2. PLEASE VERIFY LISTING OF LIGHTING CONTROLLER AND LIGHTING 110.3
3. BOXES EXTENDED IN DRYWALL MORE THAT 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
4. PLEASE VERIFY INSPECTIONS FOR PVC CONDUIT IN SLAB.
5. PLANS CALL FOR 8 NEW GFI'S WE ONLY HAVE 6
6. FILL UNUSED OPENING AND CLOSE BOX COVERS.
7. PLEASE HAVE QUALIFIED ELECTRICIAN MEET ME ON SITE.