Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
Permit Number - T06CM06508
Inspection Description - OUTDOOR LIGHTING FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2007 | OUTDOOR LIGHTING FINAL | Approved | ||
04/04/2007 | OUTDOOR LIGHTING FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY 1. REPAIR GROUNDING ELECTRODE CONDUCTOR, BONDING CONDUCTORS TO SERVICE. 2. RE-IDENTIFY ALL DISCONNECTS, SERVICE EQUIPMENT NEC 110.22, 230.70B 3. INSTALL PANEL DIRECTORY -- NEC 408.4 4. CONDUCTORS IN RACEWAYS TO BE DERATED - NEC 310.15 5. REMOVE CUT CONDUCTORS ENTERING PANEL 6. IDENTIFY PHASES ON CONDUCTORS 7. EMERGENCY LIGHTING NOT COMPLETE/WORKING NOT PER PLAN PARTIAL INSPECTION ONLY |