Permit: T06CM06508

Parcel: 105102410

Inspection Status: Approved

Inspection History: OUTDOOR LIGHTING FINAL

Date Description Inspector Results Comments
04/06/2007 OUTDOOR LIGHTING FINAL Approved
04/04/2007 OUTDOOR LIGHTING FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY
1. REPAIR GROUNDING ELECTRODE CONDUCTOR, BONDING CONDUCTORS TO SERVICE.
2. RE-IDENTIFY ALL DISCONNECTS, SERVICE EQUIPMENT
NEC 110.22, 230.70B
3. INSTALL PANEL DIRECTORY -- NEC 408.4
4. CONDUCTORS IN RACEWAYS TO BE DERATED - NEC 310.15
5. REMOVE CUT CONDUCTORS ENTERING PANEL
6. IDENTIFY PHASES ON CONDUCTORS
7. EMERGENCY LIGHTING NOT COMPLETE/WORKING
NOT PER PLAN

PARTIAL INSPECTION ONLY