Permit: T06CM06464

Parcel: 10706009C


Addresses:

1134 W MIRACLE MILE


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T06CM06464

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2007 ELECTRIC - UFER Approved IVRS - Inspection :*
04/05/2007 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONCRETE ENCASED ELECTRODE TO BE AT BOTTOM OF FOOTING OR CLOSEST TO NOT AT TOP REBAR
SEE 250.52 A-3 NEC