Permit: T06CM06457

Parcel: 10511043B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/01/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) OK TO TILE
01/31/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED BOXES THROUGHOUT - NEC 314.16
2. INSTALL ALL J-BOX COVERS
3. MC TO BE SECURED WITHIN 12" OF TERMINATION -
NEC 330.30
4. SUPPORT ALL DATA/LOW VOLTAGE WIRING OFF GRID
NEC 800.6 AND FIX LOOSE CLAMPS. REMOVE OR TAG ABANDONED LOW VOLTAGE WIRING -- NEC 800
5. PROVIDE SUPPORT WIRES FOR ALL LIGHT FIXTURES AT OPPOSITE CORNERS.