Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM06457
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK TO TILE |
|
01/31/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED BOXES THROUGHOUT - NEC 314.16 2. INSTALL ALL J-BOX COVERS 3. MC TO BE SECURED WITHIN 12" OF TERMINATION - NEC 330.30 4. SUPPORT ALL DATA/LOW VOLTAGE WIRING OFF GRID NEC 800.6 AND FIX LOOSE CLAMPS. REMOVE OR TAG ABANDONED LOW VOLTAGE WIRING -- NEC 800 5. PROVIDE SUPPORT WIRES FOR ALL LIGHT FIXTURES AT OPPOSITE CORNERS. |