Permit: T06CM06454

Parcel: 117141580


Addresses:

136 W SIMPSON ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06454

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. LEAVE PRESSURE ON GAUGE, 24 PSI
2. PROVIDE 1" CLEARANCE FROM B VENT
3. TERMINATE VENT AT CAP
4. PROVIDE SLOPE ON B VENT
5. SECURE VENT CONNECTOR TO DRAFT COLLAR AND B-VENT
WITH GALV SHEETMETAL SCREWS.
12/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL SECURE GAS DROP AT WATER HEATER.
2. ALL APPLIANCES NEED TO BE INSTALLED CORRECTLY, YOUR RANNI WATER HEATER IS FOR EXTERIOR USE ONLY
AND REQUIRES A LARGER GAS SUPPLY PIPING TO
MEET 199,000 BTU REQUIREMENTS.