Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM06454
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. LEAVE PRESSURE ON GAUGE, 24 PSI 2. PROVIDE 1" CLEARANCE FROM B VENT 3. TERMINATE VENT AT CAP 4. PROVIDE SLOPE ON B VENT 5. SECURE VENT CONNECTOR TO DRAFT COLLAR AND B-VENT WITH GALV SHEETMETAL SCREWS. |
|
12/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL SECURE GAS DROP AT WATER HEATER. 2. ALL APPLIANCES NEED TO BE INSTALLED CORRECTLY, YOUR RANNI WATER HEATER IS FOR EXTERIOR USE ONLY AND REQUIRES A LARGER GAS SUPPLY PIPING TO MEET 199,000 BTU REQUIREMENTS. |