Permit: T06CM06448

Parcel: 124060810


Addresses:

1128 E 7TH ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM06448

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2012 BUILDING - FINAL Approved IVRS - Inspection :*
06/26/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
WRONG LABELING AT CIRCUIT PANEL IN BEDROOM FOR FAN COILS
WATER HEATER IN GARAGE REQUIRES A DISCONNECTIONG MEANS WITHIN SITE OF WATER HEATER
FILL IN HOLES IN PANEL DEAD FRONT
PROVIDE HOSE CLAMPS AT BAR SINK
USE LISTED TAPE ON LINE SETS
06/08/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
05/23/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
DO NOT USE FLEX COPPER ON THE T&P DRAIN LINE
PROVIDE AN OVERFLOW SENSOR IN FAN COILS
EXTEND VENT IN CONDENATE TRAP ABOVE DRAIN PAN
PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
T STAT WIRE AT CONDENSORS TO BE IN CONDUIT
CIRCUIT BREAKERS TO LARGE FOR CONDENSORS. DO NOT USE WHITE WIRE
FINISH INSTALLING 2ND A/C SYSTEMS
CIRCUIT BREAKERS TO LARGE FOR FAN COILS. CANNOT FIND BREAKER FOR 2ND FAN COIL
PLUMBING NOT COMPLETE
FINISH ALL WORK PRIOR TO RESCHEDULING INSPECTINS