Permit: T06CM06438

Parcel: 112020470

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COUPLING STILL NOT TIGHT -- EMT NOT FITTING ALL THE WAY INTO COUPLING

FIX CORRECTION BEFORE CALLING BACK FOR FINAL.
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE LOOSE COUPLING IN EMT UNDER NORTH PANELS
2. USE PROPER FITTING (RAINTITE) INTO W.P BOXES
NOT PVC T.A AND CAULK.
03/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE APPROVED FITTINGS WITH PULLING ELLS & LB'S
2. ONLY ONE CONDUCTOR TO A LUG
3. RACEWAY TO BE COMPLETE -- 300.10