Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/17/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LOWER CLEANOUTS TO GRADE 2) FINISH LATHE ON EXTERIOR 3) NEED SHIELDED LIGHT ON WEST SIDE OF HOUSE 4) CONDENSATE LINE ON HVAC NEEDS TO BE PAINTED 5) CONDENSATE LINE HAS NEGATIVE PITCH, AND NEEDS TO BE SUPPORTED 6) BLANK ALL UNUSED VENT ON ROOF 7) FINISH PORCH AND MAKE HOLES FOR DRAINAGE 8) PAINT ALL VTR STACKS 9) SEAL AROUND THE BASE OF ALL TOILETS 10) INSTALL ALL MECHANICAL DUCT GRILLES 11) NEED 2 MORE RECEPTACLES (GFI) AT KITCHEN COUNTER SPACE |
|
| 01/21/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED 2 RECEPTACLES AT KITCHEN COUNTER SPACE 2) NEED PLANS TO INSPECT FOR ARC-FAULT AND SMOKIE CONNECTION 3) WATER HEATER MISSING TPR 40 SEAL ALL TOILETS |