Permit: T06CM06432

Parcel: 117091810


Addresses:

1043 S 5TH AV #02

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/05/2008 FRAMING Approved IVRS - Inspection :*
11/03/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUD SHOE AT LAUNDRY ROOM FOR DRAIN LAV
2) PROTECT ALL CONDUCTORS FROM PROTRUDING ? STAPLES AND ANILS
3) PROTECT ALL CONDUCTORS AT MAIN HOMERUN BUSHING
4) FIRE SEAL ALL HOLES IN TOP PLATES
5) ALL CONDUCTORS TO BE COVERED WIHT MASONRY MUT BE PROTECTED OR CHANGE TO PROPER TYPE OF WIRING
6) NEED TO NAIL AND SHIM HEADER AT ENTRANCE FOYER
7) MISSING NUT AND WASHER AT A.B. AT FOYER
8) NEED TO ADD ANCHOR BOLTS-CHECK FOR TIGHTING
12/03/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
10/08/2007 FRAMING Not ready for Inspection IVRS - Inspection :*