Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/03/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUD SHOE AT LAUNDRY ROOM FOR DRAIN LAV 2) PROTECT ALL CONDUCTORS FROM PROTRUDING ? STAPLES AND ANILS 3) PROTECT ALL CONDUCTORS AT MAIN HOMERUN BUSHING 4) FIRE SEAL ALL HOLES IN TOP PLATES 5) ALL CONDUCTORS TO BE COVERED WIHT MASONRY MUT BE PROTECTED OR CHANGE TO PROPER TYPE OF WIRING 6) NEED TO NAIL AND SHIM HEADER AT ENTRANCE FOYER 7) MISSING NUT AND WASHER AT A.B. AT FOYER 8) NEED TO ADD ANCHOR BOLTS-CHECK FOR TIGHTING |
|